A basic CO2 transcritical/subcritical commercial refrigeration system is considered, applied to cold rooms and display cabinets in a supermarket. Subcooling of the refrigerant or heat recovery from condensation can be performed, taking advantage of a large fire prevention water tank. The whole refrigeration system is modelled in a TRNSYS environment, taking into account the hourly weather data and calculating the hourly cooling load demand from display cabinets and cold rooms equipment. New types have been written to describe display cabinets and cold rooms, CO2 refrigerating units and a particular water store. Simulations consider a simple double compression cycle with liquid receiver, and other options among which an auxiliary compressor. Results show that CO2 plants are feasible and energetically acceptable in mild climates, provided that improvements to standard cycle are adopted. Furthermore, heat recovery can be effectively performed through the employment of a heat storage

Modelling commercial refrigeration systems coupled with water storage to improve energy efficiency and perform heat recovery

POLZOT, Alessio;D'AGARO, Paola;GULLO, Paride;CORTELLA, Giovanni
2016-01-01

Abstract

A basic CO2 transcritical/subcritical commercial refrigeration system is considered, applied to cold rooms and display cabinets in a supermarket. Subcooling of the refrigerant or heat recovery from condensation can be performed, taking advantage of a large fire prevention water tank. The whole refrigeration system is modelled in a TRNSYS environment, taking into account the hourly weather data and calculating the hourly cooling load demand from display cabinets and cold rooms equipment. New types have been written to describe display cabinets and cold rooms, CO2 refrigerating units and a particular water store. Simulations consider a simple double compression cycle with liquid receiver, and other options among which an auxiliary compressor. Results show that CO2 plants are feasible and energetically acceptable in mild climates, provided that improvements to standard cycle are adopted. Furthermore, heat recovery can be effectively performed through the employment of a heat storage
File in questo prodotto:
File Dimensione Formato  
rj27.pdf

non disponibili

Tipologia: Versione Editoriale (PDF)
Licenza: Non pubblico
Dimensione 1.13 MB
Formato Adobe PDF
1.13 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
rj27_sub.pdf

accesso aperto

Tipologia: Documento in Pre-print
Licenza: Creative commons
Dimensione 830.2 kB
Formato Adobe PDF
830.2 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11390/1086342
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 53
  • ???jsp.display-item.citation.isi??? 47
social impact