In recent years, CO2-based mixtures have been considered as a way to improve the performance of refrigerating plants using pure CO2 as refrigerant. Combining CO2 with a fluid with higher critical temperature generates a blend which allows to run a refrigeration plant in subcritical conditions at higher heat rejection temperature when compared to pure carbon dioxide, and consequently reach higher COP. This work evaluates from an experimental point of view two CO2/R-152a mixtures, ([90/10 %] and [95/5 %]), used as refrigerants in a single-stage refrigeration plant with and without internal heat exchanger, and compares the results to those obtained using pure CO2. The work analyses the main energy parameters of the plant for secondary fluid inlet temperature of 2.5 °C at the evaporator, and in the range from 20 °C to 40 °C with 5 °C step at the condenser/gas-cooler. The use of such mixtures, compared to the use of pure CO2, allowed to obtain a higher COP in the base cycle for heat rejection temperature above 25 °C, reaching the largest increment at the highest temperature while, when working with IHX cycle, no improvements in the COP were measured.

Experimental evaluation of CO2/R-152a mixtures in a refrigeration plant with and without IHX

Sicco, E.
Primo
;
Toffoletti, G.;Cortella, G.
Co-ultimo
;
2024-01-01

Abstract

In recent years, CO2-based mixtures have been considered as a way to improve the performance of refrigerating plants using pure CO2 as refrigerant. Combining CO2 with a fluid with higher critical temperature generates a blend which allows to run a refrigeration plant in subcritical conditions at higher heat rejection temperature when compared to pure carbon dioxide, and consequently reach higher COP. This work evaluates from an experimental point of view two CO2/R-152a mixtures, ([90/10 %] and [95/5 %]), used as refrigerants in a single-stage refrigeration plant with and without internal heat exchanger, and compares the results to those obtained using pure CO2. The work analyses the main energy parameters of the plant for secondary fluid inlet temperature of 2.5 °C at the evaporator, and in the range from 20 °C to 40 °C with 5 °C step at the condenser/gas-cooler. The use of such mixtures, compared to the use of pure CO2, allowed to obtain a higher COP in the base cycle for heat rejection temperature above 25 °C, reaching the largest increment at the highest temperature while, when working with IHX cycle, no improvements in the COP were measured.
File in questo prodotto:
File Dimensione Formato  
rj50.pdf

non disponibili

Tipologia: Versione Editoriale (PDF)
Licenza: Non pubblico
Dimensione 2.53 MB
Formato Adobe PDF
2.53 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
rj50_preprint.pdf

accesso aperto

Tipologia: Documento in Pre-print
Licenza: Creative commons
Dimensione 866.03 kB
Formato Adobe PDF
866.03 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11390/1269984
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 6
  • ???jsp.display-item.citation.isi??? 6
social impact