In this paper, we propose a new family of modular hybrid resonant switched tank converters (HRSTC) to perform high fixed-ratio 48 V-to-intermediate bus voltage down-conversion in data center applications. These topologies exploit a modular approach to address the challenge of achieving compact and efficient high voltage conversion ratio in a configurable way. The HRSTC leverages the use of a multi-tapped autotransformer (MTA) to enhance the conversion ratio of the switched-capacitor converter (SCC) structure. Additionally, using the residual energy of the MTA leakage and magnetizing inductances, quasi-zero current switching (Q-ZCS) and zero voltage switching (ZVS) commutation is achieved. After introducing, deriving, and analyzing the HRSTC structures, we present a prototype converter for 48-to-3.4 V nominal voltage conversion at 260 A maximum output current. The developed prototype achieves a peak efficiency of 96.6 % and a power density of 920 W/inch3. This prototype validates the expected operation and performance of the HRSTC.

Hybrid Resonant Switched Tank Converters for High Step-Down Voltage Conversion

Balutto M.;Saggini S.;
2024-01-01

Abstract

In this paper, we propose a new family of modular hybrid resonant switched tank converters (HRSTC) to perform high fixed-ratio 48 V-to-intermediate bus voltage down-conversion in data center applications. These topologies exploit a modular approach to address the challenge of achieving compact and efficient high voltage conversion ratio in a configurable way. The HRSTC leverages the use of a multi-tapped autotransformer (MTA) to enhance the conversion ratio of the switched-capacitor converter (SCC) structure. Additionally, using the residual energy of the MTA leakage and magnetizing inductances, quasi-zero current switching (Q-ZCS) and zero voltage switching (ZVS) commutation is achieved. After introducing, deriving, and analyzing the HRSTC structures, we present a prototype converter for 48-to-3.4 V nominal voltage conversion at 260 A maximum output current. The developed prototype achieves a peak efficiency of 96.6 % and a power density of 920 W/inch3. This prototype validates the expected operation and performance of the HRSTC.
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11390/1287684
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? ND
social impact